TransformerHigh voltage cabinetLow voltage cabinetOutdoor complete equipment

XGN66

PRODUCT PARAMETERS
1. Cold rolled steel plate or angle steel (used for welding cabinets);
2. Aluminum zinc coated steel plate or galvanized steel plate (used for assembling cabinets);
3. Stainless steel plate (non magnetic); cabinet
4. Aluminum plate (non magnetic).

Hotline:+86-570-4982909 銷售熱線:+86-570-4982880
Description
Feature
Parameter
High voltage distribution cabinets refer to electrical products used for power generation, transmission, distribution, energy conversion, and consumption in the power system, with functions such as on/off, control, or protection, and voltage levels ranging from 3.6kV to 550kV. Most power supply bureaus and substations use high-voltage switchgear, which is then led out from the low-voltage side of the transformer to the low-voltage distribution cabinet. The low-voltage distribution cabinet is then connected to various electrical equipment such as distribution boards, control boxes, and switch boxes to meet the design functional requirements of the distribution equipment.
Product technical features:
1. Adopting heat shrink insulation materials and epoxy coating insulation process, optimizing electrode shape, compact cabinet structure, and reducing floor area;
2. The switchgear cabinet body is made of high-quality cold-rolled steel, which is formed by CNC sheet metal processing and connected by high-strength bolts and nuts and rivet nuts. The surface of the components is sprayed with plastic or galvanized technology;
3. It can be matched with domestic ZN85-40.5 vacuum circuit breakers and foreign SF1, SF2, and FP system sulfur hexafluoride circuit breakers to meet the needs of different users;
4. Each functional compartment of the switchgear is sealed with metal plates and equipped with independent pressure release channels;
5. Circuit breakers, grounding switches, and other operations can be carried out when the switchgear is closed, achieving door closing operation;
6. The structural adaptability of the switchgear is strong, with over 198 main wiring schemes that can meet the needs of different users;
7. There is a mechanical interlocking device between the handcart, circuit breaker, grounding switch, and rear cabinet door to prevent misoperation. The "five prevention" functions are complete, safe and reliable

Number

Project Name

Unit

Technical Parameter

1

Rated voltage

kv

10

2

Maximum operating voltage

kV

12

3

Rated frequency

Hz

50

 4

1min power frequency withstand voltage

W

Phase to phase and phase to ground 42, isolation fracture 48

5

Lightning impulse withstand voltage

W

Phase to phase and phase to ground 75, isolation fracture 85

6

Rated current of main busbar

A

630

7

load

switch

Rated current

A

630

8

Mechanical life

second

5000

9

Breaking no-load transformer capacity

KNA

1250

10

Rated thermal stability current

MA

20(4S)

11

Rated dynamic stable current

kA

50(Peak value)

12

Rated making current

A

50(1Peak value)

13

combination

electrical equipment

Maximum rated current of fuse

A

100

14

Rated transfer current

A

1500(2000)

15

Rated short-circuit breaking current

kA

31.5

16

Distribution fuse model

 

SOLAJ-12(XRNTO-10)

17

Maximum rated capacity of matched transformer

kVA

1250